Circuit Breakers and Switchgear MCQs with Explanations and Theory
This chapter covers the switchgear and protection questions that recruitment tests repeat most: what a circuit breaker, isolator, contactor, fuse and relay each do; how an arc forms and how it is put out; air-break, oil, air-blast, SF₆ and vacuum breakers; contact materials and contact resistance; the trip sequence and the timing terms (opening, arcing, break, clearing and dead time); breaker ratings, breaking capacity and simple fault-level numericals; recovery voltage, TRV, RRRV and current chopping; fuses and HRC fuses; protective relays (overcurrent, thermal, differential, distance, Buchholz), CTs and plug setting multiplier; neutral earthing and symmetrical components; and overvoltages, surge arresters and travelling waves. Every numerical uses one or two steps.
What you will learn
- State the job of each switchgear device (breaker, isolator, earthing switch, contactor, fuse, relay) and the safe switching sequence.
- Explain arc formation, ionization and deionization, and the high-resistance and current-zero methods of arc interruption.
- Compare air-break, bulk-oil, minimum-oil, air-blast, SF₆ and vacuum circuit breakers by medium, principle and application.
- Use the timing terms and T = 1/f to find break time, clearing time and cycles.
- Calculate breaking capacity (√3 V I), making current, rated current and fault level (S/Zpu).
- Explain recovery voltage, TRV, RRRV and current chopping, and find f₀ = 1/(2π√LC) and V = I√(L/C).
- Describe fuse terms (fusing factor, pre-arcing and arcing time, HRC, current limiting) and Preece’s law.
- Identify relay types and protection schemes, and find CT ratio, primary pickup, PSM and apparent impedance.
- Compare neutral-earthing methods, use I₀ = (Ia + Ib + Ic)/3, and explain surge arresters, surge impedance and reflections.
Topics in this chapter
| # | Topic | Access |
|---|---|---|
| 15.1 | Switchgear and Its Devices What switchgear is, and the separate jobs of the circuit breaker, isolator, earthing switch, contactor, fuse and relay. | Free (below) |
| 15.2 | The Arc: Formation and Properties Why an arc forms when contacts part, where its charge carriers come from, how they are removed, and how an arc behaves electrically. | Premium |
| 15.3 | Methods of Arc Interruption The high-resistance method and the current-zero method, magnetic blowout and arc chutes, gas blast, spark suppression, and why DC is harder to break. | Premium |
| 15.4 | Contacts, Contact Resistance and Busbars Main and arcing contacts and their materials, contact resistance and heating, insulation resistance, and copper versus aluminium busbars. | Premium |
| 15.5 | Air-Break, Oil and Air-Blast Breakers How air-break, bulk-oil, minimum-oil and air-blast breakers put out the arc, their typical voltages, advantages and drawbacks, and insulating-oil properties. | Premium |
| 15.6 | SF₆ and Vacuum Circuit Breakers Properties of SF₆ gas, puffer and double-pressure designs, SF₆ drawbacks, and the construction and working of the vacuum interrupter. | Premium |
| 15.7 | Trip Circuit, Operating Sequence and Timing How a relay trips a breaker, auxiliary contacts and supervision, and the timing terms: opening, arcing, break, clearing, closing and dead time. | Premium |
| 15.8 | Breaker Ratings and Fault Calculations Rated voltage and current, breaking, making and short-time ratings, breaking capacity in MVA, and simple rated-current and fault-level numericals. | Premium |
| 15.9 | Recovery Voltage, TRV, RRRV and Current Chopping The voltages that appear across the contacts after current zero, why low power factor makes interruption harder, and the overvoltage caused by current chopping. | Premium |
| 15.10 | Fuses and HRC Fuses How a fuse works, fuse terms (fusing factor, pre-arcing and arcing time), element materials, Preece’s law, HRC and current-limiting fuses, and motor and transformer fusing. | Premium |
| 15.11 | Protective Relays: Qualities and Types Qualities of a protection system, relay operating principles, time characteristics, thermal relays, pickup and reset, and overcurrent and directional relays. | Premium |
| 15.12 | Protection Schemes, CTs and Relay Settings Differential (Merz–Price), pilot-wire and carrier schemes, distance relays, the Buchholz relay, negative-sequence and frequency relays, CT/VT safety and PSM numericals. | Premium |
| 15.13 | Neutral Earthing, Faults and Symmetrical Components Why and how the neutral is earthed, ungrounded systems and arcing grounds, earth-fault current, zero- and negative-sequence currents, and current-limiting reactors. | Premium |
| 15.14 | Overvoltages, Surge Protection and Travelling Waves Causes of overvoltage, surge arresters, horn gaps and sphere gaps, surge impedance and reflection of travelling waves, surge modifiers, and the safe switching sequence. | Premium |
Free topic 15.1: Switchgear and Its Devices
What switchgear is, and the separate jobs of the circuit breaker, isolator, earthing switch, contactor, fuse and relay.
The general name for all apparatus used to switch, control, isolate and protect electrical circuits: circuit breakers, isolators (disconnectors), earthing switches, fuses, contactors, current and voltage transformers, protective relays and their control wiring.
A switching device that can MAKE, CARRY and BREAK both normal load current and abnormal (fault) current within its ratings. It must also withstand the heat and the mechanical forces of fault current until it opens.
Who does what
| Device | Job | Limitation |
|---|---|---|
| Circuit breaker | Makes, carries and breaks load and fault current | Must be rated for the system voltage, current and fault level |
| Isolator (disconnector) | Gives a visible, safe isolation gap | Operated off-load; never breaks load or fault current |
| Earthing switch | Connects an isolated circuit to earth | Interlocked; closed only on a dead, isolated circuit |
| Contactor | Frequent switching of loads such as motors | Needs a fuse or breaker for short-circuit protection |
| Fuse | Melts and breaks overcurrent automatically | One-time device; must be replaced |
| Relay | Detects the fault and closes the trip circuit | Does not break the main current itself |
Breakers are named by the medium in which the arc is put out: air (air-break), oil (bulk oil and minimum oil), compressed air (air-blast), SF₆ gas and vacuum. The operating mechanism (spring, pneumatic, hydraulic or electromagnetic) is a separate choice and must not be confused with the medium. Contactors are classified by their mechanism: electromagnetic, pneumatic or electropneumatic.
Voltage classes: low voltage (LV) AC equipment is rated up to 1 kV (1000 V). Typical application examples: air-break breakers at LV; bulk-oil breakers up to about 33 kV; vacuum breakers at 11–33 kV; air-blast and SF₆ breakers at 132, 220 and 400 kV. These are typical examples, not strict limits. Flameproof switchgear is built for explosive atmospheres such as coal mines.
Solved Circuit Breakers and Switchgear MCQs
10 of the 292 questions in this chapter. Choose an option, then read the explanation.
Show answer
Answer: C. To make, carry and interrupt load and fault current within its ratings A circuit breaker is the switching device that can close (make), carry and open (break) both normal current and fault current, as long as these are within its ratings. Why not the others: a visible off-load gap is the job of an isolator; measuring current is done by a CT; power-factor correction is done by capacitors.
Show answer
Answer: D. Closes its contacts to energize the breaker trip coil The relay detects the abnormal quantity and closes the trip circuit; the trip coil then opens the breaker, and the BREAKER interrupts the power current. Why not the others: relay contacts are far too small to break fault current; isolators are never used to clear faults; a relay does not limit current. Exam tip: relay detects, breaker interrupts.
Show answer
Answer: A. 1 kV AC equipment rated up to 1000 V (1 kV) is classed as low voltage; above that it is medium or high voltage. Why not the others: 3.3 kV and 11 kV are medium-voltage distribution levels; 33 kV is sub-transmission.
Show answer
Answer: B. Vacuum Electromagnetic, pneumatic and electropneumatic describe how the contacts are moved. “Vacuum” describes the medium in which the arc is broken (a vacuum contactor), not the mechanism. Exam tip: medium and mechanism are different classifications.
Show answer
Answer: C. Air, oil, SF₆ and vacuum Breakers are named by their quenching medium: air (air-break and air-blast), insulating oil, SF₆ gas and vacuum. Why not the others: mica, porcelain, glass and PVC are solid insulators; water, glycerine and paper are not arc-quenching media; copper, silver and tungsten are contact metals.
Show answer
Answer: C. Air-break isolator An air-break isolator (disconnector) opens an air gap to isolate a circuit, but only off-load; it has no arc-quenching ability for fault current. Why not the others: SF₆, vacuum and air-blast breakers are all designed to interrupt fault current.
Show answer
Answer: B. Off-load, with no or negligible current An isolator has no arc-quenching ability. It is opened only after the breaker has interrupted the current, to provide a safe, visible isolation gap. Why not the others: opening it on load or under fault would draw a dangerous arc; it is never a substitute for a breaker.
Show answer
Answer: D. A breaker can interrupt fault current; a contactor is for frequent load switching A contactor is built for very many load operations (for example starting motors) but cannot break large fault currents, so it needs a fuse or breaker for short-circuit protection. A breaker is rated to break fault current. Why not the others: they reverse the roles or confuse a breaker with an isolator.
Show answer
Answer: C. In explosive atmospheres such as coal mines Flameproof enclosures are designed so that an internal spark or explosion cannot ignite the surrounding gas or dust — essential in mines and some chemical plants. The equipment must be certified for that atmosphere.
Show answer
Answer: A. Reducing the electric field strength across the gap Impact ionization happens when electrons accelerated by the field gain enough energy to knock electrons out of gas atoms. A weaker field accelerates them less, so fewer collisions ionize. Why not the others: a stronger field and more energetic electrons increase ionization; a hotter gas adds thermal ionization.