Transformers MCQs with Explanations and Theory
This chapter covers the transformer questions that recruitment tests repeat most: the working principle and turns ratio; construction, core materials, oil and cooling; the EMF equation and the effect of voltage and frequency on flux, core size and kVA rating; no-load current and its phasor; the equivalent circuit, referring impedances, leakage reactance and impedance matching; hysteresis, eddy-current and copper losses; efficiency, maximum efficiency and all-day efficiency; voltage regulation, including zero and negative regulation; the open-circuit, short-circuit and back-to-back tests; parallel operation and load sharing; autotransformers and tertiary windings; current and potential transformers; the Buchholz relay, breather, taps and other fittings; and three-phase connections, vector groups, open delta and the Scott connection. Every numerical uses one or two steps.
What you will learn
- Explain mutual induction and use V₁/V₂ = N₁/N₂ = I₂/I₁ for ideal transformers, including cascades.
- Use E = 4.44 f N Φm to find flux, and predict how voltage and frequency change flux, core size, losses and kVA rating.
- Describe the no-load current, its components and phase angle, and refer impedances between windings with a².
- Separate core and copper losses, calculate efficiency, the load for maximum efficiency and all-day efficiency.
- Calculate approximate regulation for lagging and leading loads, and the conditions for zero and maximum regulation.
- Interpret open-circuit, short-circuit and back-to-back test results and find the equivalent-circuit parameters.
- State the conditions for parallel operation and divide a load between transformers by their impedances.
- Compare autotransformers with two-winding transformers, and state the uses and safety rules of CTs and PTs.
- Identify the fittings and protection of oil-filled transformers, and work with star/delta connections, vector groups, open delta and the Scott connection.
Topics in this chapter
| # | Topic | Access |
|---|---|---|
| 13.1 | Working Principle and the Ideal Transformer How a transformer transfers AC power by mutual induction, the turns, voltage and current ratios, cascades and dot polarity. | Free (below) |
| 13.2 | Construction, Core Materials and Cooling Core-type and shell-type construction, core materials, winding arrangement, insulating oil and cooling methods. | Premium |
| 13.3 | EMF Equation, Flux, Frequency and kVA Rating E = 4.44 f N Φm, why flux is set by V/f, how frequency and flux density decide core size, and how voltage and frequency change the kVA rating. | Premium |
| 13.4 | No-Load Operation and the No-Load Phasor The exciting current, its core-loss and magnetizing components, phase angles, the effect of reluctance and air gaps, and peaky magnetizing current. | Premium |
| 13.5 | Equivalent Circuit, Leakage and Impedance Matching Referring resistance and reactance with a², leakage flux, impedance matching, mutual inductance, several secondaries and frequency limits. | Premium |
| 13.6 | Core and Copper Losses Hysteresis and eddy-current loss, laminations, the effect of voltage and frequency, copper loss and its square law, harmonics and thermal limits. | Premium |
| 13.7 | Efficiency, Maximum Efficiency and All-Day Efficiency The efficiency formula, the load and current for maximum efficiency, power versus distribution transformer design, and energy (all-day) efficiency. | Premium |
| 13.8 | Voltage Regulation Definition of regulation, the approximate formula for lagging and leading loads, zero, negative and maximum regulation, and the Kapp diagram. | Premium |
| 13.9 | Open-Circuit, Short-Circuit and Back-to-Back Tests What the OC and SC tests measure and why, the equivalent-circuit formulas, Sumpner’s test, other tests and percentage impedance. | Premium |
| 13.10 | Parallel Operation and Load Sharing Essential and desirable conditions for paralleling, what goes wrong when they are not met, and how load divides between units. | Premium |
| 13.11 | Autotransformers, Boosters and Tertiary Windings One-winding transformers, copper saving, conducted and induced power, kVA rating when reconnected, drawbacks, boosters and tertiary windings. | Premium |
| 13.12 | Current and Potential Transformers How CTs and PTs are connected, their standard secondary values, burden, accuracy classes and the safety rules. | Premium |
| 13.13 | Fittings, Accessories and Protection Conservator, breather, Buchholz relay, tap changer, bushings, surge protection, transformer hum, differential protection and inrush. | Premium |
| 13.14 | Three-Phase Transformers and Vector Groups Star and delta relations, line-voltage ratios of the four connections, vector groups, three-phase units versus banks and the open-delta connection. | Premium |
| 13.15 | Scott (T) Connection How two single-phase transformers convert three-phase to two-phase, the main and teaser transformers, and the 0.866 rule. | Premium |
Free topic 13.1: Working Principle and the Ideal Transformer
How a transformer transfers AC power by mutual induction, the turns, voltage and current ratios, cascades and dot polarity.
A static device that transfers AC electrical energy from one circuit to another by mutual induction, at the SAME frequency. It can step voltage up or down (and current the opposite way), isolate circuits or match impedances. It does not generate power.
How it works: an alternating current in the primary sets up an alternating flux in a low-reluctance iron core. This mutual flux links the secondary and induces an EMF in it (Faraday’s law); Lenz’s law fixes its direction. When a load is connected, the secondary current tries to reduce the flux, so the primary draws extra current to keep the flux almost constant. On steady DC there is no changing flux, so no transformer action — only a large current limited by the winding resistance, which can burn the winding.
| Primary and secondary turns | ||
| Primary and secondary voltages | V | |
| Primary and secondary currents | A |
Turns and current
- A 200-turn primary on 200 V must give 400 V.
- N₂ = 200 × 400/200 = 400 turns.
- If the load draws 5 A, I₁ = 5 × 400/200 = 10 A.
Secondary current from turns
- 50 kVA, 3300 V primary, N₁ = 834, N₂ = 58.
- V₂ = 3300 × 58/834 = 229.5 V.
- I₂ = 50 000/229.5 ≈ 218 A (primary current = 50 000/3300 ≈ 15 A).
Ideal transformer assumptions
- No winding resistance (no copper loss).
- No leakage flux — all flux links both windings.
- No core loss and infinite permeability (zero no-load current).
- So: same EMF per turn in every winding, and input power = output power.
Cascades: when transformers are connected one after another, their ratios multiply. 1:5 followed by 1:3 gives a gain of 15; 5:1 followed by 10:1 gives 50:1.
Dot polarity: dots mark the terminals that are positive at the same instant. Voltages measured dot-to-undotted on both windings are in phase (0°). If both currents are taken as entering the dots, then v₁ = a·v₂ and i₁ = −i₂/a: the ampere-turns oppose each other. A 1:1 isolation transformer has ratio 1 and only separates the circuits.
Solved Transformers MCQs
10 of the 336 questions in this chapter. Choose an option, then read the explanation.
Show answer
Answer: A. 15 Given: stage gains 5 and 3. Formula: overall gain = product of stage gains. Solution: 5 × 3 = 15. Answer: 15. Why not the others: 8 adds the gains; 5/3 and 2 divide or subtract them.
Show answer
Answer: D. 200 Given: N₁ = 100, V₁ = 200 V, V₂ = 400 V. Formula: N₂ = N₁ × V₂/V₁. Solution: N₂ = 100 × 400/200 = 200. Answer: 200 turns. Why not the others: 100 means no step-up; 50 inverts the ratio; 400 copies the voltage value.
Show answer
Answer: B. Voltage A step-up transformer has more secondary turns, so V₂ > V₁. Because V₁I₁ ≈ V₂I₂, the current is stepped down in the same ratio. Why not the others: frequency never changes; power cannot increase (it falls slightly due to losses); power factor is set by the load.
Show answer
Answer: B. Fewer turns than the primary V₂/V₁ = N₂/N₁. For V₂ < V₁ the secondary needs fewer turns. It carries more current, so its wire is thicker. Why not the others: more turns gives step-up; equal turns gives a 1:1 ratio.
Show answer
Answer: B. In phase Dot marking means that, at every instant, the dotted ends of both windings are positive together. So the two voltages, measured from dot to undotted end, are in phase. Why not the others: 180° would be the case if one winding were measured from its undotted end; 90° and 120° have no meaning for a single-phase transformer.
Show answer
Answer: D. 218 A Given: S = 50 kVA, V₁ = 3300 V, N₁ = 834, N₂ = 58. Steps: V₂ = 3300 × 58/834 = 229.5 V. I₂ = 50 000/229.5 ≈ 218 A. Answer: about 218 A. Why not the others: 15 A is the PRIMARY current (50 000/3300); 30 A and 438 A come from ratio slips.
Show answer
Answer: C. 50:1 Formula: overall ratio = product of the stage ratios. Solution: 5 × 10 = 50 → 50:1. Answer: 50:1. Why not the others: 15:1 adds the ratios; 2:1 divides them; 2500:1 squares the product.
Show answer
Answer: C. Sinusoidal at the same frequency, scaled by the turns ratio An ideal transformer simply multiplies the instantaneous voltage by N₂/N₁. The waveform shape and frequency stay the same; with dot polarity the two voltages are in phase. Why not the others: transformers do not change waveform to square or DC, and never change frequency.
Show answer
Answer: B. Equal Both windings are linked by the same mutual flux, so each turn has the same EMF: 4.44 f Φm. The secondary has more volts only because it has more turns. Why not the others: volts per turn do not depend on which winding it is.
Show answer
Answer: D. Output frequency ÷ input frequency A transformer never changes frequency, so f₂/f₁ = 1. Why not the others: in a step-up transformer N₂/N₁ and E₂/E₁ are greater than 1, and I₂/I₁ is less than 1.